Firesafe Standard Specification
In
order to ensure Firesafe fire rated ductwork is correctly specified,
several factors
should
be carefully considered.
1. Define
the type of system - Smoke extract, car park extract, kitchen
extract, pressurisation, general ventilation, dual ventilation/smoke
extraction system.
2. State
the fire rating to BS476 Part 24: 1987 in minutes for:
3. Define
if the system is Duct Type A (Fire Outside) or Duct Type B (Fire
Inside and Outside).
4. Define
the operating pressure limits of the ductwork as defined by HVCA
specification DW144.
|
|
(Class A
up to 500pa positive or 500pa negative ) |
|
|
(Class B
up to 1000pa positive or 750pa negative) |
|
|
(Class C
up to 2000pa positive or 750pa negative) |
5. Define
the requirements for access doors requirement for maintenance and
cleaning as defined by HVCA specification DW144 table 25.
|
Pro-Forma
Specification |
|
The
.....(1) ..... ductwork should be Firesafe fire rated duct as manufactured
and
installed by C Caswell Engineering Services Limited to comply with
BS476 Part 24 (1987)
for
.....(2)..... mins stability .....(2)..... mins integrity and
.....(2)..... mins insulation.
The
ductwork should be capable of providing type .....(3)..... fire
containment and under normal
operating
conditions should conform to .....(4).....pressure classification of
the current HVCA DW144
specification
access doors for maintenance and cleaning should conform to HVCA DW144
table 25 .....(5).....
|
|